User Manual
8
Threaded PICVs
Typical applications Actuators Data sheet 4.5 mm 5 mm
– Chilled ceilings
– Fan coil units
– Zone control
STA..
SUE21P
N4884
A6V11780777
100 N 100 N
Operating voltage
Positioning signal
Positioning time [s]
STA SUE21P
AC 230 V 2-position 210
12 STA23 SUE21P
AC/DC 24 V
2-position/PDM 270
–
STA73 –
PN 25 1...90 °C
Without pressure
testing points
With pressure
testing points DN
G
[Inch]
⩒
min
[l/h]
⩒
100
[l/h]
∆p
min
[kPa]
∆p
max
[kPa]
∆p
min
[kPa]
∆p
max
[kPa]
Data sheet A6V11877580
VQP46.10L0.5 VQP46.10L0.5Q 10 ½ 30 520 30 600 30 600
VQP46.15L0.5 VQP46.15L0.5Q 15 ¾ 30 520 28 600 28 600
VQP46.15L1.3 VQP46.15L1.3Q 15 ¾ 300 1300 28 600 28 600
VQP46.20L1.5 VQP46.20L1.5Q
20 1 320 1500 35 600
35 600
VQP46.25L1.8 VQP46.25L1.8Q
25 1 ¼ 620 1800 31 600
31 600
PN 25 1...90 °C
Without pressure
testing points
With pressure
testing points DN
Rp
[Inch]
⩒
min
[l/h]
⩒
100
[l/h]
∆p
min
[kPa]
∆p
max
[kPa]
∆p
min
[kPa]
∆p
max
[kPa]
Data sheet A6V11877580
VQI46.15L0.5 VQI46.15L0.5Q 15 ½ 30 520 28 600 28 600
VQI46.15L1.3 VQI46.15L1.3Q 15 ½ 300 1300 28 600 28 600
VQI46.20L1.5 VQI46.20L1.5Q
20 ¾ 320 1500 35 600 35 600
VQI46.25L1.8 VQI46.25L1.8Q
25 1 620 1800 31 600
31 600
Intelligent Valves
Typical applications Valve type Operating voltage Positioning signal Interface
– Heating groups
– Air handling units
EVG4U10E.. DN15-50 AC/DC 24 V
0...10 V, 2...10 V,
4...20 mA
BACnet over UDP/IP
Ethernet to building operator
EVF4U20E.. DN65-125 AC/DC 24 V
0...10 V, 2...10 V,
4...20 mA
BACnet over UDP/IP
Ethernet to building operator
PN 16 1...120 °C
DN
k
vs
[m
3
/h]
⩒
min
[m
3
/h]
⩒
100
[m
3
/h]
∆p
s
[kPa]
∆p
max
[kPa]
Data sheet A6V11444716
EVG4U10E015 15 4 0.45 1.5 1400 600
1)
EVG4U10E020 20 5 0.9 3 1400 600
1)
EVG4U10E025 25 10 1.35 4.5 1400 600
1)
EVG4U10E032 32 11 2.1 7 1000 600
1)
EVG4U10E040 40 26 3.45 11.5 800 600
1)
EVG4U10E050 50 30 5.4 18 600 600
1)
EVF4U20E065 65 55 9 30 1600 600
1)
EVF4U20E080 80 80 14.5 48 1600 600
1)
EVF4U20E100 100 113 22.5 75 1600 600
1)
EVF4U20E125 125 142 36 120 1600 600
1)
Typical applications Valve type Operating voltage Positioning signal Interface
– Heating groups
– Air handling units
EXG4U10E.. DN15-50 AC/DC 24 V
0…10 V, 2…10 V,
4…20 mA
BACnet over UDP/IP
Ethernet to building operator
EXF4U20E.. DN65-100 AC/DC 24 V
0…10 V, 2…10 V,
4…20 mA
BACnet over UDP/IP
Ethernet to building operator
PN 16
1...120 °C
DN
k
vs
[m
3
/h]
⩒
min
[m
3
/h]
⩒
100
[m
3
/h]
∆p
max
[kPa]
EXG4U10E015 15 3.7 0.36 1.2 200
EXG4U10E020 20 4 0.6 2 200
EXG4U10E025 25 8 0.96 3.2 200
EXG4U10E032 32 10 1.5 5 200
EXG4U10E040 40 18 2.4 8 200
EXG4U10E050 50 26 3.6 12 200
EXF4U20E065 65 55 6 20 150
EXF4U20E080 80 80 9.6 32 75
EXF4U20E100 100 113 15 50 125
1)
The safety measures must be observed according to the data sheet