User Manual

26
Valve sizing and actuator selection
Basic hydronic circuit
1
Determine the type
of hydronic circuit
Throttling
circuit
Injection
circuit with
2-port valve
Mixing circuit
Mixing circuit with
xed premixing
Diverting
circuit
Injection
circuit with
3-port valve
For valve sizing
relevant variable
ow path
Δ
p
Primary pump ü Primary pump Primary pump ü Primary pump
HVAC plants and consumers
Heating
Surface/oor heating
n
n n
outdated
Heating plant (primary)
n n n n n
outdated outdated
Zone control, heating
n
outdated
Heating groups
n n n n n
Generation of heat energy
n
n
Heat exchanger water-water
n
uncommon uncommon uncommon uncommon
Ventilation and air conditioning plants
Air handling unit
n n n n
outdated outdated
Fan coil unit
n
outdated outdated
Cooling coil
dehumidifying
n
uncommon uncommon
Reheating coil
n n
uncommon uncommon uncommon uncommon outdated outdated
Preheating coil
n
uncommon uncommon uncommon uncommon outdated
VAV
n
outdated outdated
Zone control
n
outdated outdated
Chiller plants
Surface/oor cooling
n
outdated
Generation of cooling
energy
n
n
Cooling towers
n
outdated uncommon
Zone control, cooling
n
outdated
District heating and cooling
District heating, primary
n
uncommon uncommon uncommon
District heating, secondary
n n
uncommon uncommon
District cooling, primary
n
uncommon uncommon uncommon
District cooling, secondary
n n
uncommon uncommon
Hot water
Hot water directly
n
n
Header
Differential
pressure header
pressurized low-pressure pressureless low-pressure pressureless pressurized
Volumetric ow variable variable constant