User Manual
10
Flanged PICVs
Typical applications Actuators Data sheet 20 mm 20 / 40 mm 40 mm
– District heating
– Heating groups
– Air handling units
SAX..P..
SQV91P..
SAV..P..
N4509
N4833
N4510
500 N 1100 N 1100 N
Operating
voltage
Positioning
signal
Positioning time [s]
Spring return
function [s]
SAX SQV SAV
AC 230 V
3-position 30 – 120 – SAX31P03 – SAV31P00
3-position – 40/80 – 30 – SQV91P40
1)
–
3-position – 40/80 – 30 – SQV91P30
2)
–
AC/DC 24 V
3-position 30 – 120 – SAX81P03 – SAV81P00
3-position – 40/80 – 30 – SQV91P40
1)
–
3-position – 40/80 – 30 – SQV91P30
2)
–
0...10 V, 4...20 mA
30 – 120 – SAX61P03 – SAV61P00
0...10 V, 4...20 mA
– 40/80 – 30 – SQV91P40
1)
–
0...10 V, 4...20 mA
– 40/80 – 30 – SQV91P30
2)
–
Modbus
30 – 120 –
SAX61P03/
MO
–
SAV61P00/
MO
PN 16
1...120 °C
DN
V
·
min
[m
3
/h]
V
·
100
[m
3
/h]
∆p
min
[kPa]
∆p
s
/∆p
max
[kPa]
∆p
s
/∆p
max
[kPa]
∆p
s
/∆p
max
[kPa]
Data sheet A6V11466366
VPF44.50F15
3)
50 3.7 14.3 25 700/600 700/600 –
VPF44.50F25
3)
50 5.7 24.6 55 700/600 700/600 –
VPF44.65F25
3)
65 4.5 24.4 32 700/600 700/600 –
VPF44.65F35
3)
65 6.4 37.7 50 700/600 700/600 –
VPF44.80F35
3)
80 6.8 35.7 22 700/600 700/600 –
VPF44.80F45
3)
80 8.5 49 40 700/600 700/600 –
VPF44.100F70 100 12.2 69.6 33 – 700/600 700/600
VPF44.100F90 100 14.8 90.9 75 – 700/600 700/600
VPF43.125F110 125 18.5 110 35 – 600 600
VPF43.125F135 125 23 135 53 – 600 600
VPF43.150F160 150 25.6 148 35 – 600 600
VPF43.150F200 150 32 195 65 – 600 600
VPF43.200F210
4)
200 95 210 32 – 600 600
VPF43.200F280
4)
200 130 280 78 – 600 600
PN 25
1...120 °C
DN
V
·
min
[m
3
/h]
V
·
100
[m
3
/h]
∆p
min
[kPa]
∆p
s
/∆p
max
[kPa]
∆p
s
/∆p
max
[kPa]
∆p
s
/∆p
max
[kPa]
Data sheet N4316
VPF54.50F15 50 3.7 14.3 25 700/600 700/600 –
VPF54.50F25 50 5.7 24.6 55 700/600 700/600 –
VPF54.65F25 65 4.5 24.4 32 700/600 700/600 –
VPF54.65F35 65 6.4 37.7 50 700/600 700/600 –
VPF54.80F35 80 6.8 34.7 22 700/600 700/600 –
VPF54.80F45 80 8.5 49.9 40 700/600 700/600 –
VPF54.100F70 100 12.2 69.6 33 – 700/600 700/600
VPF54.100F90 100 14.8 90.9 45 – 700/600 700/600
VPF53.125F110 125 18.5 110 35 – 600 600
VPF53.125F135 125 23 135 53 – 600 600
VPF53.150F160 150 25.6 148 35 – 600 600
VPF53.150F200 150 32 195 65 – 600 600
VPF53.200F210
4)
200 95 210 32 – 600 600
VPF53.200F280
4)
200 130 280 78 – 600 600
1)
Fail-safe function: valve closed
2)
Fail-safe function: valve open
3)
Concerns valve type from series B
4)
Max. medium temperature 110 °C
5)
Optimized for oor heating systems
6)
In control mode (warm-up time) min. running time approx. 30 s/mm
k
v
= nominal ow rate of cold water (5...30 °C) through the valve at the respective stroke and a differential pressure of 100 kPa (1 bar)
The selected k
v
values of the radiator valves can be easily and precisely set on the valve head in 5 steps + N (fully open).