Flanged PICVs
Typical applications Actuators Data sheet 20 mm 20 / 40 mm 40 mm
– District heating
Heating groups
Air handling units
SAX..P..
SQV91P..
SAV..P..
N4509
N4833
N4510
500 N 1100 N 1100 N
Operating
voltage
Positioning
signal
Positioning time [s]
Spring return
function [s]
SAX SQV SAV
AC 230 V
3-position 30 120 SAX31P03 SAV31P00
3-position 40/80 30 SQV91P40
1)
3-position 40/80 30 SQV91P30
2)
AC/DC 24 V
3-position 30 120 SAX81P03 SAV81P00
3-position 40/80 30 SQV91P40
1)
3-position 40/80 30 SQV91P30
2)
0...10 V, 4...20 mA
30 120 SAX61P03 SAV61P00
0...10 V, 4...20 mA
40/80 30 SQV91P40
1)
0...10 V, 4...20 mA
40/80 30 SQV91P30
2)
Modbus
30 120
SAX61P03/
MO
SAV61P00/
MO
PN 16
1...120 °C
DN
V
·
min
[m
3
/h]
V
·
100
[m
3
/h]
∆p
min
[kPa]
∆p
s
/∆p
max
[kPa]
∆p
s
/∆p
max
[kPa]
∆p
s
/∆p
max
[kPa]
Data sheet A6V11466366
VPF44.50F15
3)
50 3.7 14.3 25 700/600 700/600
VPF44.50F25
3)
50 5.7 24.6 55 700/600 700/600
VPF44.65F25
3)
65 4.5 24.4 32 700/600 700/600
VPF44.65F35
3)
65 6.4 37.7 50 700/600 700/600
VPF44.80F35
3)
80 6.8 35.7 22 700/600 700/600
VPF44.80F45
3)
80 8.5 49 40 700/600 700/600
VPF44.100F70 100 12.2 69.6 33 700/600 700/600
VPF44.100F90 100 14.8 90.9 75 700/600 700/600
VPF43.125F110 125 18.5 110 35 600 600
VPF43.125F135 125 23 135 53 600 600
VPF43.150F160 150 25.6 148 35 600 600
VPF43.150F200 150 32 195 65 600 600
VPF43.200F210
4)
200 95 210 32 600 600
VPF43.200F280
4)
200 130 280 78 600 600
PN 25
1...120 °C
DN
V
·
min
[m
3
/h]
V
·
100
[m
3
/h]
∆p
min
[kPa]
∆p
s
/∆p
max
[kPa]
∆p
s
/∆p
max
[kPa]
∆p
s
/∆p
max
[kPa]
Data sheet N4316
VPF54.50F15 50 3.7 14.3 25 700/600 700/600
VPF54.50F25 50 5.7 24.6 55 700/600 700/600
VPF54.65F25 65 4.5 24.4 32 700/600 700/600
VPF54.65F35 65 6.4 37.7 50 700/600 700/600
VPF54.80F35 80 6.8 34.7 22 700/600 700/600
VPF54.80F45 80 8.5 49.9 40 700/600 700/600
VPF54.100F70 100 12.2 69.6 33 700/600 700/600
VPF54.100F90 100 14.8 90.9 45 700/600 700/600
VPF53.125F110 125 18.5 110 35 600 600
VPF53.125F135 125 23 135 53 600 600
VPF53.150F160 150 25.6 148 35 600 600
VPF53.150F200 150 32 195 65 600 600
VPF53.200F210
4)
200 95 210 32 600 600
VPF53.200F280
4)
200 130 280 78 600 600
1)
Fail-safe function: valve closed
2)
Fail-safe function: valve open
3)
Concerns valve type from series B
4)
Max. medium temperature 110 °C
5)
Optimized for oor heating systems
6)
In control mode (warm-up time) min. running time approx. 30 s/mm
k
v
= nominal ow rate of cold water (5...30 °C) through the valve at the respective stroke and a differential pressure of 100 kPa (1 bar)
The selected k
v
values of the radiator valves can be easily and precisely set on the valve head in 5 steps + N (fully open).