Operating Instructions
Technical data
Technical data Actuator controls
78 | 80
A6V12052002
Features and functions
Motor protection evaluation
Standard
Monitoring the motor temperature in combination
with thermoswitches within actuator motor.
Electrical connection
Standard
AUMA plug/socket connector with screw-type
connection
Cable entry threads
Standard
NPT threads
Wiring diagram
See the nameplate.
Further options for Non-intrusive version with MWG in the actuator
Setting of limit and torque switching via local controls
Torque feedback signal
Galvanically isolated analog output 0/4 – 20 mA
(load maximum 500 Ω).
Service conditions
Uses
Indoor and outdoor use
permissible
Mounting position
Any position
Installation altitude
≤ 2,000 m above sea level
> 2,000 m above sea level, on
request
Ambient temperature
See the actuator controls
nameplate
Humidity
Up to 100% relative humidity
across the entire permissible
temperature range
Enclosure protection according to
EN 60529
Standard
IP68
According to AUMA definition,
enclosure protection IP68 meets
the following requirements:
● Depth of water: Maximum 8
m head of water
● Duration of continuous
immersion in water:
Maximum 96 hours
● Up to 10 operations during
continuous immersion
● Modulating duty is not
possible during continuous
immersion.
● For exact version, see the
actuator controls name plate.
Pollution degree according to
IEC 60664-1
Pollution degree 4 (when closed),
pollution degree 2 (internal)