Operating Instructions

Technical data
Technical data Actuator controls
76 | 80
A6V12052002
Features and functions
Analog input
2 analog inputs:
With positioner/process controller option: Input of
actual position value/actual process value as
continuous values between 0/4 and 20 mA.
Local controls
Standard
Selector switch: LOCAL - OFF - REMOTE
(lockable in all three positions)
Push buttons OPEN, STOP, CLOSE, RESET
Local Stop: The actuator can be stopped via push
button STOP of local controls if the selector switch is
in position REMOTE. (Not activated when leaving
the factory.)
6 Indication lights.
End position and running indication CLOSED
(yellow), torque fault CLOSE (red), motor
protection tripped (red), torque fault OPEN
(red), end position and running indication OPEN
(green), Bluetooth (blue)
Graphic LC display: illuminated
Bluetooth
Communication interface
Bluetooth class II chip, version 2.1: With a range up
to 10 m in industrial environments, supports the SPP
Bluetooth profile (Serial Port Profile).
Application functions
Standard
Selectable type of seating, limit or torque
seating for end positions OPEN and CLOSED
Torque by-pass: Adjustable duration (with
adjustable peak torque during start-up time)
Start and end of stepping mode as well as ON
and OFF times can be set individually for
directions OPEN and CLOSE, 1 to 1,800
seconds
Any 8 intermediate positions: can be set
between 0 and 100 %, reaction and signal
behavior programmable
Running indication blinking: can be set
Options
Modulating SV
units only
Positioner
Position setpoint via analog input
0/4 20 mA
Programmable behavior on loss of signal
Automatic adaptation of dead band
(adaptive behavior selectable)
Split range operation
MODE input for selecting between OPEN-
CLOSE and setpoint control
PID process controller: with adaptive positioner,
via 0/4 20 mA analog inputs for process
setpoint and actual process value
Multiport valve: Up to 16 positions, signals
(pulse or edge)
Automatic deblocking: Up to 5 operation trials,
travel time in opposite direction can be set
Static and dynamic torque recording for both
rotation directions with torque measurement
flange as additional accessory