Operating Instructions
Technical data
Technical data Actuator controls
76 | 80
A6V12052002
Features and functions
Analog input
2 analog inputs:
With positioner/process controller option: Input of
actual position value/actual process value as
continuous values between 0/4 and 20 mA.
Local controls
Standard
● Selector switch: LOCAL - OFF - REMOTE
(lockable in all three positions)
● Push buttons OPEN, STOP, CLOSE, RESET
Local Stop: The actuator can be stopped via push
button STOP of local controls if the selector switch is
in position REMOTE. (Not activated when leaving
the factory.)
– 6 Indication lights.
End position and running indication CLOSED
(yellow), torque fault CLOSE (red), motor
protection tripped (red), torque fault OPEN
(red), end position and running indication OPEN
(green), Bluetooth (blue)
– Graphic LC display: illuminated
Bluetooth
Communication interface
Bluetooth class II chip, version 2.1: With a range up
to 10 m in industrial environments, supports the SPP
Bluetooth profile (Serial Port Profile).
Application functions
Standard
● Selectable type of seating, limit or torque
seating for end positions OPEN and CLOSED
● Torque by-pass: Adjustable duration (with
adjustable peak torque during start-up time)
Start and end of stepping mode as well as ON
and OFF times can be set individually for
directions OPEN and CLOSE, 1 to 1,800
seconds
● Any 8 intermediate positions: can be set
between 0 and 100 %, reaction and signal
behavior programmable
● Running indication blinking: can be set
Options
Modulating SV
units only
● Positioner
– Position setpoint via analog input
0/4 –20 mA
– Programmable behavior on loss of signal
– Automatic adaptation of dead band
(adaptive behavior selectable)
– Split range operation
– MODE input for selecting between OPEN-
CLOSE and setpoint control
● PID process controller: with adaptive positioner,
via 0/4 – 20 mA analog inputs for process
setpoint and actual process value
● Multiport valve: Up to 16 positions, signals
(pulse or edge)
● Automatic deblocking: Up to 5 operation trials,
travel time in opposite direction can be set
● Static and dynamic torque recording for both
rotation directions with torque measurement
flange as additional accessory