Operating Instructions
Technical data
Technical data Actuator controls
A6V12052002
75 | 80
Technical data Actuator controls
Features and functions
Power supply
See the nameplate
Permissible variation of mains voltage: ±10%
Permissible variation of mains voltage: ±30%
(optional)
Permissible variation of mains frequency: ±5%
External electronics supply
Option
24 Vdc +20%/–15%
Current consumption: Basic version approx. 250 mA,
with options up to 500 mA.
External power supply must have reinforced
insulation against mains voltage in accordance with
IEC 61010-1 and may only be supplied by a circuit
limited to 150 VA in accordance with IEC 61010-1.
Current consumption
Current consumption of the actuator controls
depending on mains voltage:
For permissible variation of mains voltage of ±10 %:
100 to 120 Vac = maximum 740 mA
Overvoltage category
Category III according to IEC 60364-4-443
Rated power
The actuator controls are designed for the nominal
motor power, see the motor nameplate.
The reversing contactors are designed for a lifetime
of 2 million starts. For applications requiring a high
Switchgear
Standard
Reversing contactors (mechanically and electrically
interlocked) for AUMA power classes A1/A2 number
of starts, we recommend the use of thyristor
units.For the assignment of AUMA power classes,
see the Electrical data on the actuator.
Control inputs
6 digital inputs: OPEN, STOP, CLOSE,
EMERGENCY (using opto-isolator, thereof OPEN,
STOP, CLOSE with one common and EMERGENCY
without common, respect minimum pulse duration for
modulating actuators)
Control voltage/current
consumption
Standard
24 Vdc, current consumption: approx. 10 mA per
input
All input signals must be supplied with the same
potential.
Status signals (Output signals)
Standard
6 programmable output contacts:
6 potential-free change-over contacts without one
common, per contact max. 250 Vac, 5A (resistive
load)
All output signals must be supplied with the same
potential.
Voltage output
Standard
Option
Auxiliary voltage 24 Vdc: max. 100 mA for supply of
control inputs, galvanically isolated from internal
voltage supply.
Auxiliary voltage 115 Vsv: max. 30 mA for supply of
control inputs, galvanically isolated from internal
voltage supply/
(Not possible in combination with PTC tripping
device.)
Analog output
2 analog outputs:
With position transmitter option: Output of travel and
torque as continuous values between 0/4 and 20 Ma.