Operating Instructions
Corrective action
Fault indications and warning indications
A6V12052002
63 | 80
Faults and Failure
Indication on display
Description/cause
Remedy
Configuration error
Collective signal 11:
Configuration error has occurred.
Press push button Details to
display a list of individual
indications.
For a description of the individual
signals, see the Manual
(Operation and setting).
Config. error REMOTE
Collective signal 22:
Configuration error has occurred.
Press push button Details to
display a list of individual
indications.
For a description of the individual
signals, see the Manual
(Operation and setting).
Internal error
Collective signal 14:
Internal error has occurred.
AUMA service
Press push button Details to
display a list of individual
indications.
For a description of the individual
signals, see the Manual
(Operation and setting).
Torque fault CLOSE
Torque fault in direction CLOSE
Perform one of the following
measures:
● Issue operation command in
direction OPEN.
● Set selector switch to
position Local control
(LOCAL) and reset fault
indication using push button
RESET.
Torque fault OPEN
Torque fault in direction OPEN
Perform one of the following
measures:
● Issue operation command in
direction CLOSE.
● Set selector switch to
position Local control
(LOCAL) and reset fault
indication via push button
RESET.
Phase fault
● When connecting to a 3-ph
AC system and with internal
24 Vdc supply of the
electronics: Phase 2 is
missing.
● When connecting to a 3-ph
or 1-ph AC system and with
external 24 Vdc supply of the
electronics: One of the
phases L1, L2 or L3 is
missing.
Test/connect phases.