Operating Instructions

Corrective action
Fault indications and warning indications
A6V12052002
61 | 80
Indication on display
Description/cause
Remedy
S0008
Out of specification
Collective signal 07:
Indication according to NAMUR
recommendation NE 107
Actuator operates outside the
normal operation conditions.
For indicated value > 0: Press push button
Details.
For details, see the <Warnings and Out of
specification> table.
S0009
Function check
Collective signal 08:
Indication according to NAMUR
recommendation NE 107
The actuator is being worked
on; output signals are
temporarily invalid.
For indicated value > 0: Press push button
Details.
For details, see the <Not ready REMOTE and
Function check> table.
S0010
Maintenance required
Collective signal 09:
Indication according to NAMUR
recommendation NE 107
Recommendation to perform
maintenance.
For indicated value > 0: Press push button
Details to display a list of detailed indications.
S0011
Failure
Collective signal 10:
Indication according to NAMUR
recommendation NE 107
Actuator function failure, output
signals are invalid.
For indicated value > 0: Press push button
Details to display a list of detailed indications.
For details, see the <Faults and Failure> table.
Indication on display
Description/cause
Remedy
Config. warning
Collective signal 06:
Possible cause:
Configuration setting is
incorrect.
The device can still be operated
with restrictions.
Press push button Details to display a list of
indi-vidual indications.
For a description of the individual signals, see
the Manual (Operation and setting).
Internal warning
Collective signal 15:
Device warnings
The device can still be operated
with restrictions.
Press push button Details for a list of
individual indications.
For a description of the individual signals, see
the Manual (Operation and setting).
24 Vdc external
The external 24 Vdc voltage
supply of the controls has
exceeded the power supply
limits.
Check 24 Vdc voltage supply.
Wrn op.mode run time
Warning on time maximum
running time/h exceeded
Check modulating behavior of actuator.
Check parameter Perm. run time M0356,
re-set if required.
Wrn op.mode starts
Warning on time max. number
of motor starts (starts) exceeded
Check modulating behavior of actuator.
Check parameter Permissible starts
M0357, reset if required.
Failure behav. active
The failure behavior is active
since all required setpoints and
actual values are incorrect.
Verify signals:
Setpoint E1
Actual value E2
Actual process value E4
Wrn input AIN 1
Warning: Loss of signal
analogue input 1
Check wiring.