Operating Instructions
Commissioning (basic settings)
Limit switching: set
A6V12052002
49 | 80
Information
The following fault signals are issued if the torque setting performed has been reached
in mid-travel:
● In the display of the local controls: Status indication S0007 Fault = Torque fault
OPEN or Torque fault CLOSE
The fault must be acknowledged before the operation can be resumed. The
acknowledgement is made:
● either by an operation command in the opposite direction.
– For Torque fault OPEN: Operation command in the CLOSE direction
– For Torque fault CLOSE: Operation command in the OPEN direction
● or, in case the torque applied is lower than the preset tripping torque:
– in selector switch position Local control (LOCAL) via push button RESET.
– in selector switch position Remote control (REMOTE):
via a digital (I/O interface) with the Reset command if a digital input is
configured for RESET signal.
Limit switching: set
NOTICE
Valve damage at valve/gearbox due to incorrect setting!
When setting with motor operation: Stop the actuator prior reaching end of travel
(press the STOP push button).
Customer settings M0041
Limit switching M0010
● Set end pos.CLOSED? M0084
● Set end pos. OPEN? M0085
Select main menu
1. Set selector switch to the 0 (OFF) position.
2. Press push button C and hold it down for approximately 3 seconds.
Display goes to main menu and indicates: ▶ Display...