Operating Instructions
Commissioning (basic settings)
Torque switching: set
48 | 80
A6V12052002
Customer settings M0041
Torque switching M0013
Trip torque CLOSE M0088
Trip torque OPEN M0089
Default value: According to order data
Setting range: Torque range according to actuator name plate
Torque switching: set
1. Set the selector switch to the 0 (OFF) position to select the main menu.
2. Press push button C Setup and hold it down for approximately 3 seconds.
The display goes to the main menu and indicates: ▶ Display...
3. Select parameter either:
– click via the menu to parameter, or
– using direct display: press and enter ID M0088.
Display indicates: Trip torque CLOSE
4. Use Up ▲ Down ▼ to select:
– Trip torque CLOSE
– Trip torque OPEN
The black triangle ▶ indicates the current selection.
5. Press Ok.
Display shows the set value.
The bottom row indicates: Edit Esc
6. Press Edit.
Display indicates:
Specialist (4) → continue with Step 7
in bottom row Up ▲ Down ▼ Esc → continue with Step 11
7. Use Up ▲ Down ▼ to select user login:
Information: Required user level: Specialist (4) or higher.
The symbols have the following meanings:
-black triangle: ▶ = current setting
-white triangle: ▷ = selection (not saved yet)
8. Press Ok.
Display indicates: Password 0***
9. Enter password (→ enter password).
Display shows the set value.
The bottom row indicates: Edit Esc
10. Press Edit.
11. Enter new value for tripping torque via Up ▲ Down ▼.
Information: The adjustable torque range is shown in round brackets.
12. Save new value via Save.
The tripping torque is set.
13. Back to step 4 (CLOSED or OPEN): Press Esc.