Operating Instructions
Signals (output signals)
Status signals using output contacts (digital outputs)
44 | 80
A6V12052002
Signals (output signals)
Status signals using output contacts (digital
outputs)
Characteristics
Output contacts send status signals (for example, reaching the end positions, selector
switch position, faults, and so on) as binary signals to the control room.
Status signals only have two states: active or inactive. Active means that the
conditions for the signal are fulfilled.
Assignment of outputs
The output contacts (outputs DOUT 1 – 12) can be assigned to various signals.
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Signal DOUT 1 M0109
Default values:
● Signal DOUT 1 = Fault
● Signal DOUT 2 = End position CLOSED
● Signal DOUT 3 = End position OPEN
● Signal DOUT 4 = Selector sw. REMOTE
● Signal DOUT 5 = Torque fault CLOSE
● Signal DOUT 6 = Torque fault OPEN
● Signal DOUT 7 = Thermal fault
● Signal DOUT 8 = OPEN
● Signal DOUT 9 = Limit switch CLOSED
● Signal DOUT 10 = Limit switch OPEN
● Signal DOUT 11 = Torque sw. CLOSED
● Signal DOUT 12 = Torque sw. OPEN
Coding the outputs
The output signals Coding DOUT 1 – Coding DOUT 12 can be set either to high active
or low active.
● High active = output contact closed = signal active Low active = output contact
open = signal active
● Signal active means that the conditions for the signal are fulfilled.
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Coding DOUT 1 M0102