Operating Instructions
Indications
Indications in the display
38 | 80
A6V12052002
Pivot point axis
The pivot points and their operation behavior (operation profile) are shown on the pivot
point axis by means of symbols.
The symbols are only displayed if at least one of the following functions is activated:
● Operation profile M0294
● Timer CLOSE M0156
● Timer OPEN M0206
Figure 32: Examples: on the left pivot points (intermediate positions); on the right stepping mode.
Table 7: Symbols along the pivot point axis.
Symbol
Pivot point (intermediate position) with
operation profile
Stepping mode
|
Pivot point without reaction
End of stepping mode
◀
Stop during operation in CLOSE direction
Start of stepping mode in CLOSE
direction
▶
Stop during operation in OPEN direction
Start of stepping mode in OPEN
direction
◆
Stop during operation in directions OPEN
and CLOSE
–
◁
Pause for operation in CLOSE direction
–
▷
Pause for operation in OPEN direction
–
◇
Pause for operation in OPEN and CLOSE
directions
–
Multiport valve positions (S0017)
In case of active multiport valve function, the display S0017 indicates a second bar
graph with set positions (valve connections) above the actual position value E2.
Positions (P1, P2, ...) are displayed with a black triangle . Push buttons are
used to select positions. Both positions and the actual position value E2 are displayed
in degrees.
Figure 33: Status indication for multiport valve (example P4 = 180°)
P
(P1, P2, ...) selected position (1, 2, ...)
(– –) no position selected
E2
Actual position value
Status indications according to AUMA classification
These indications are available if the parameter Diagnostic classification M0539 is set
to AUMA.