Operating Instructions
Operation
Push button menu navigation (for settings and indications)
28 | 80
A6V12052002
Remote actuator operation
CAUTION
Risk of immediate actuator operation when switching on!
Risk of personal injuries or damage to the valve
● If the actuator starts unexpectedly: Immediately turn the selector switch to the 0
(OFF) position.
● Check input signals and functions.
Set the selector switch to the Remote control (REMOTE) position.
▶The actuator can now be operated with the remote control, though operation
commands (OPEN, STOP, CLOSE) or analog setpoints (for example, 0 to 20 mA).
Information For actuators equipped with a positioner, it is possible to change over
between OPEN - CLOSE control (Remote OPEN-CLOSE) and setpoint control
(Remote SETPOINT). Selection is made using the MODE input, for example, based
on a 24 Vdc signal (see the wiring diagram).
Push button menu navigation (for settings and
indications)
Use push buttons [1 through 4] of the local controls for display and setting menu
navigation.
Set the selector switch [5] to the 0 (OFF) position when navigating through the menu.
The bottom row of the display [6] serves as navigation support and explains which
push buttons [1 – 4] are used for menu navigation.
[1–4] Push buttons or navigation support
[5] Selector switch