Operating Instructions

Electrical connection
Basic information
A6V12052002
23 | 80
Mains voltage
Maximum current consumption
Permissible variation of the mains
voltage
±10%
30%
100 to 120 Vac
750 mA
1,000 mA
Switchgear
(switchgear with power class)
1)
Rated power
max. protection
Reversing contactor A1
up to 1.5 kW
16
A (gL/gG)
Reversing contactor A2
up to 7.5 kW
32
A (gL/gG)
Reversing contactor A3
up to 15 kW
63
A (gL/gG)
Thyristor B1
up to 1.5 kW
16
A (g/R)
I²t<1,500A²s
Thyristor B2
up to 3 kW
32
A (g/R)
I²t<1,500A²s
Thyristor B3
up to 5.5 kW
63
A (g/R)
I²t<5,000A²s
1)
The AUMA power class (A1, B1, ...) is indicated on the actuator controls name plate