Operating Instructions
Assembly
Mounting positions of local controls
20 | 80
A6V12052002
Table 2: Tightening Torques for Screws.
Threads
Tightening torque lb-ft (Nm)
Strength class A2-80/A4–80
M6
7 (10)
M8
17 (24)
M10
35 (48)
M12
60 (82)
M16
148 (200)
M20
289 (392)
Mounting positions of local controls
Figure 9: Mounting positions.
The mounting position of the local controls is implemented according to the order. If,
after mounting the actuator to the valve or the gearbox on site, the local controls are
not positioned properly, the mounting position can be changed at a later date. Four
mounting positions shifted by respectively 90° are possible (maximum 180° into one
direction).
Mounting positions: modify
DANGER
Hazardous voltage! Risk of electric shock.
Disconnect device from the power source before opening.