Operating Instructions

Technical data
Technical data Actuator controls
78 | 80
A6V12052002
Features and functions
Motor protection evaluation
Standard
Monitoring the motor temperature in combination
with thermoswitches within actuator motor.
Electrical connection
Standard
AUMA plug/socket connector with screw-type
connection
Cable entry threads
Standard
NPT threads
Wiring diagram
See the nameplate.
Setting of limit and torque switching via local controls
Torque feedback signal
Galvanically isolated analog output 0/4 20 mA
(load maximum 500 Ω).
Service conditions
Uses
Indoor and outdoor use
permissible
Mounting position
Any position
Installation altitude
≤ 2,000 m above sea level
> 2,000 m above sea level, on
request
Ambient temperature
See the actuator controls
nameplate
Humidity
Up to 100% relative humidity
across the entire permissible
temperature range
Enclosure protection according to
EN 60529
Standard
IP68
According to AUMA definition,
enclosure protection IP68 meets
the following requirements:
Depth of water: Maximum 8
m head of water
Duration of continuous
immersion in water:
Maximum 96 hours
Up to 10 operations during
continuous immersion
Modulating duty is not
possible during continuous
immersion.
For exact version, see the
actuator controls name plate.
Pollution degree according to
IEC 60664-1
Pollution degree 4 (when closed),
pollution degree 2 (internal)