Operating Instructions
Commissioning (settings/options in the actuator)
Mechanical position indicator (self-adjusting)
56 | 80
A6V12052002
Mechanical position indicator (self-adjusting)
Figure 48: Mechanical position indicator (self-adjusting)
The self-adjusting mechanical position indicator shows the valve position with an
arrow . When correctly set, the arrow points to the symbols (OPEN) or
(CLOSED) in the end positions.
Information The position indications is housed in the actuator switch compartment.
Opening the switch compartment for manual setting is only necessary if the gear stage
setting must be modified of if the factory settings of pre-defined end position CLOSED
(or OPEN) must be adapted when commissioning.
Mechanical position indicator: set
Move valve to end position CLOSED.
Push both lower discs with the symbols (OPEN) and (CLOSED) towards
each other. The disc with the arrow is thereby is driven:
Figure 49: Setting position in CLOSED.
Move actuator to end position OPEN.
➥ The arrow rotates in OPEN direction, driving the indicator disc with symbol
(OPEN) until the actuator stops in the OPEN position.
Figure 50: Operation in direction OPEN (left) and position OPEN (right)
Check settings: