Operating Instructions
Commissioning (settings/options in the actuator)
Switch compartment: open/close
A6V12052002
55 | 80
Commissioning (settings/options in the
actuator)
For actuators without mechanical position indicator (cover without indicator glass), no
settings are required within the actuator when commissioning.
When equipped with the self-adjusting mechanical position indicator [A], the position
indicator automatically adjusts upon the initial operation (for example, from CLOSED
to OPEN). This self-adjustment is generally performed when setting the limit switches
(approaching the end positions). Manual setting and consequently opening the switch
compartment is not necessary when commissioning.
In case the mechanical position indicator integrated within the actuator is NOT self-
adjusting [B], the switch compartment must be opened for mechanical position
indication adjustment when commissioning.
Figure 46: Mechanical position indicators
[A] Mechanical position indicator (self-adjusting)
[B] Mechanical position indicator using indicator mark (not self-adjusting)
Switch compartment: open/close
Figure 47: Open/close switch compartment
[A] Mechanical position indication (self-adjusting)
[B] Mechanical position indication via indicator mark
Open 1. Loosen screws [2] and remove cover [1] from the switch compartment.
Close 2. Clean sealing faces of housing and cover.
Check whether O-ring [3] is in good condition, replace if damaged.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and insert it
correctly.
Place cover [1] on switch compartment.
Fasten screws [2] evenly crosswise.