Commissioning (basic settings)
Test run
54 | 80
A6V12052002
Correctly fit/screw on threaded plug [1] and seal [2] or protective cap for stem
protection tube [4], fasten thread.
Limit switching: check
1. Set selector switch to position Local control (LOCAL).
2. Operate actuator using push buttons OPEN, STOP, CLOSE.
➥ The limit switching is set correctly if (default indication):
● the yellow indication light/LED1 is illuminated in end position CLOSED
● the green indication light/LED5 is illuminated in end position OPEN
● the indication lights go out after travelling into opposite direction.
➥ The limit switching is set incorrectly if:
● the actuator comes to a standstill before reaching the end position
● one of the red indication lights/LEDs is illuminated (torque fault)
● the status indication S0007 in the display signals a fault.
If the end position setting is incorrect: Reset limit switching.