Operating Instructions
Commissioning (basic settings)
Test run
A6V12052002
51 | 80
Make selection:
● Edit → back to Step 9: Set end position CLOSED "once again"
● Esc → back to Step 4; either set end position OPEN or exit the menu.
Set end position OPEN CMD0010
◈
Reset end position OPEN:
For large strokes: Set selector switch in position Local control (LOCAL) and operate
actuator in motor operation via push button (OPEN) in direction of the end
position.
Information: Stop the actuator before reaching end of travel (press STOP push
button to avoid damage.
● Engage manual operation.
● Turn the handwheel until the valve is open.
● Turn the handwheel by approximately half a turn (overrun) in the opposite
direction of end position.
● Set selector switch to the 0 (OFF) position.
Display indicates: Set end pos. OPEN? Yes No
1. Press Yes to accept new end position setting.
Display indicates: End pos. OPEN set!
The right LED is illuminated (standard version) and thus indicates that the end position
OPEN setting is complete.
◈
Make selection:
Edit → back to step 12: Set end position OPEN "once again"
Esc → back to step 4; either set end position CLOSED or exit the menu.
Information If an end position cannot be set: Check the type of control unit in
actuator.
Test run
Only perform the test run once all settings previously described have been performed.
The direction of rotation can be checked at the position indicator if available. (Chapter
<Direction of rotation at mechanical position indicator: check>)
The direction of rotation must be checked at the hollow shaft/stem if no mechanical
position indicator is available. (Chapter <Direction of rotation at hollow shaft/stem:
check>)