Operating Instructions
Commissioning (basic settings)
Type of seating: set
46 | 80
A6V12052002
Commissioning (basic settings)
1. Set selector switch to the 0 (OFF) position.
Information: The selector switch is not a mains switch. When positioned to 0
(OFF), the actuator cannot be operated. The controls' power supply is maintained.
2. Switch on the power supply.
Information: Observe heat-up time for ambient temperatures below -22°F (-
30°C).
3. Perform basic settings.
Type of seating: set
NOTICE
Valve damage due to incorrect setting!
The type of seating must suit the valve. Only change the setting with the consent of
the valve manufacturer.
Customer settings M0041
Type of seating M0012
End position CLOSED M0086
End position OPEN M0087
Defaut value: Limit
Setting values:
Limit
Seating in end positions via limit switching.
Torque
Seating in end positions via torque switching.
Type of seating: set
1. Set selector switch to position 0 (OFF) to Select main menu.
2. Press push button C Setup and hold it down for approx. 3 seconds.
Display goes to main menu and indicates: ▶ Display...
3. Select parameter either:
– click via the menu to parameter, or
– via direct display: Press and enter ID M0086 or M0087
Display indicates: End position CLOSED
4. Use Up ▲ Down ▼ to select:
– End position CLOSED
– End position OPEN
The black triangle ▶ indicates the current selection.