Operating Instructions
Indications
Indication lights of local controls
A6V12052002
41 | 80
Figure 40: Failure.
For further information, see <Corrective action>.
Indication lights of local controls
Figure 41: Arrangement and meaning of indication lights.
[1]
Marking with symbols (standard)
[2]
Marking with figures 1 – 6 (option)
1
End position CLOSED reached (blinking: operation in direction CLOSE)
2
Tc
Torque fault CLOSE
3
Motor protection tripped
4
To
Torque fault OPEN
5
End position OPEN reached (blinking: operation in direction OPEN)
6
Bluetooth connection
Modify indication light assignment (indications)
Different indications can be assigned to LEDs 1 – 5.
Device configuration M0053
Local controls M0159
● Indication light 1 (left) M0093
● Indication light 2 M0094
● Indication light 3 M0095
● Indication light 4 M0096
● Indication light 5 (right) M0097
● Signal intermediate position M0167
Default values:
Indication light 1 (left) = End p. CLOSED, blink
Indication light 2 = Torque fault CLOSE
Indication light 3 = Thermal fault
Indication light 4 = Torque fault OPEN