CAUTION
When wiring an A-Series Industrial Electric Actuator for two-position (on/off) control
and the power to the actuator is commanded to be off, you must ensure that there is
no extraneous or leakage voltage between hot and common. Leakage voltage
greater than 3 Vac can cause actuator failure.
When wiring an A-Series Industrial Electric Actuator for two-position control, the
controller should use at minimum a one-second time delay for command signal
reversal. Instantaneous command reversals may cause actuator failure.