User's Manual

2-18 9700 POWER METER USER’S GUIDE
Setpoint Framework
This portion of the configuration provided setpoints to monitor phase
current, voltage unbalance and kW sliding window demand. Using
WinPM, upper limits are input for each parameter. If the measured value
goes above the specified limit for at least 30 seconds, WinPm annunciates
an alarm.
Displayed/Accessible by Default
Description of
Parameter or Function
WinPM MGT
Module
Name
Module
Label
Output
Register Label
Over kW SW Demand
l
Relative Setpoint #1 Over kW swd Over kW swd
Over Phase A Current
l
Relative Setpoint #2 Over I a Over I a
Over Phase B Current
l
Relative Setpoint #3 Over I b Over I b
Over Phase C Current
l
Relative Setpoint #4 Over I c Over I c
Over Voltage Unbalance
l
Relative Setpoint #5 Over V unbal Over V unbal
Nominal kW SW Demand
l
External Numeric #1 kW swd
nominal
kW swd
nominal
Nominal Phase A Current
l
External Numeric #2 I a nominal I a nominal
Nominal Phase B Current
l
External Numeric #3 I b nominal I b nominal
Nominal Phase C Current
l
External Numeric #4 I c nominal I c nominal
Nominal Voltage unbalance
l
External Numeric #5 V unbal nominal V unbal nominal
Over-demand monitoring
enable
l
External Boolean #7 Over kW Enble Over kW Enble
Over-current monitoring
enable
l
External Boolean #8 Over Amp
Enble
Over Amp
Enble
Over-voltage unbalance
monitoring enable
l
External Boolean #9 Over Vunb
Enble
Over Vunb
Enble