Brochure

21
www.usa.siemens.com/hvac
Part Number Description
590-500 Housing to Adapt to 1/2" Conduit, Use with 590 Types
Optional accessories help
speed up installation.
Accessories
590-500
Used in building energy
management systems, these
transducers are capable of
measuring pressures with the
accuracy necessary for proper
building pressurization and
airflow control. Their 0 to 10
Vdc analog output is
compatible with all energy
management systems.
With 10 psi proof pressure on
all ranges, they are available in
five different air pressure
ranges. Static accuracy is ±1%
full scale in normal ambient
temperature environments.
The units are temperature
compensated to less than
±0.033% FS/°F of thermal error
over the temperature range of
0°F to +150°F. 1% accuracy, or
better, improves variable air
volume system performance.
QBM81
Part Number Version Output Pressure Accuracy Category Power
Relative
Differential
0 to10 Vdc
4 to 20 mA
Relay Contact
LCD Display
Adjustable
Water Column
Percentage
Basic
Standard
High Quality
24 Vac
0 to 10 Vdc
QBM81-3
1
n n n
0.08 to 1.2"
QBM81-5
1
n n n
0.2 to 2.0"
QBM81-10
1
n n n
0.4 to 4.0"
590-501
n n n
0 to 5"
1.0
n n
590-502
n n n
0 to 2"
1.0
n n
590-503
n n n
0 to 1"
1.0
n n
590-505
n n n
0 to +/- 0.25"
1.0
n n
590-506
2
n n n
0 to 5"
1.0
n n
590-507
2
n n n
0 to 2"
1.0
n n
590-508
2
n n n
0 to 1"
1.0
n n
590-510
2
n n n
0 to +/- 0.25"
1.0
n n
590-780
n n n
0 to 1"
0.4
n n
590-781
n n n
0 to 0.65"
0.4
n n
590-782
n n n
0 to 0.5"
0.4
n n
1. Includes mounting accessories
2. Comes with 590-500 housing for conduit
Air Pressure Sensors
590-501