Datasheet
Switching frequency / at digital output / maximum 10Hz
Transfer rate
● 1 / for fast Ethernet
10Mbit/s
● 2 / for fast Ethernet
100Mbit/s
Measuring inputs
Outer conductors and neutral conductors internal
resistance / for voltage measurement
6MΩ
Measurable supply voltage
● between (PE)N and L / at AC / maximum rated
value
400V
● between the outer conductors / at AC /
maximum
831V
● between the outer conductors / at AC /
maximum rated value
690V
Voltage measuring range extension / with external
voltage transformers
Yes
Current measuring range extension / with external
current transformers
Yes
Measuring category / for voltage measurement CATIII
Supply voltage / between the outer conductors / at
AC / maximum permissible
831V
Consumed active power / for current measurement /
per phase
2.5mW
Continuous current / at AC / maximum permissible 10A
Measuring category / for current measurement CATIII
Zero-point suppression / for current measurement 0 ... 10 %
● for neutral conductor current
0.0 % to 10.0 % (from Vrated, Irated)
Relative measurable current / at AC
● minimum
1%
● maximum
200%
Apparent power consumption / for current
measurement
● with measuring range 5 A / per phase
2V·A
Measuring procedure / for current measurement TRMS
Measurable current / 1 / at AC / Rated value 1A
Connections
Type of connectable conductor cross-sections
● at the measurement inputs for voltage / at AWG
conductors / solid
Screw connection
● at the measurement inputs for voltage / solid
2.5 mm²
● at the measurement inputs for voltage / finely
stranded / with core end processing
2.5 mm²
● at the measurement inputs for current / at AWG
conductors / solid
Screw connection
7KM5212-6BA00-1EA2 Subject to change without notice
Page 4/
9
01/14/2019 © Copyright Siemens