Datasheet
Voltage curve Sinusoidal or distorted
Measurable line frequency / initial value 45Hz
Measurable line frequency / Full-scale value 65Hz
Measuring procedure / for voltage measurement TRMS
Supply voltage
Supply voltage frequency / rated value
● minimum
45Hz
● maximum
65Hz
Type of voltage / of the supply voltage AC/DC
Measuring category / for supply voltage CATIII
Apparent power consumption
● with expansion module / maximum
6V·A
● without expansion module / typical
6V·A
Relative symmetrical tolerance / of the supply voltage 20%
Protection class
Protection class IP
● on the front
IP40
● Rear side
IP20
Operating resource protection class / when installed II
Electricity
Measurable current / 2 / at AC / Rated value 10A
Suitability
Suitability for operation Installation in stationary control panels in closed rooms
Adjustable time period / minimum 50ms
Product function
Product function
● Illuminance of display backlighting adjustable
Yes
● Time-controlled reduction of the illuminance of
display backlighting possible
Yes
● reactive power measurement
Yes
● frequency measurement
Yes
● pulse measurement
Yes
● Display contrast adjustable
Yes
● voltage measurement
Yes
● Current measurement
Yes
● active power measurement
Yes
Display and operation
Design of the display LCD
Number of keys 4
Color / of the background of the display white
7KM5212-6BA00-1EA2 Subject to change without notice
Page 2/
9
01/14/2019 © Copyright Siemens