Datasheet

6SL3210-1KE21-3UB1
Data sheet for SINAMICS G120C
MLFB-Ordering data
Figure similar
Switching level: 1→0
Standard digital inputs
Number
Max. inrush current
Switching level: 0→1
Inputs / outputs
Fail-safe digital inputs
Number
Digital outputs
Number as transistor
Output (resistive load)
Number as relay changeover contact
Output (resistive load)
Analog / digital inputs
Number
Compliance with standards
CE marking
Standards
Number
Analog outputs
PTC/ KTY interface
1
15 mA
5 V
11 V
6
1
1
EMC Directive 2004/108/EC, Low-Voltage
Directive 2006/95/EC
UL, cUL, CE, C-Tick (RCM)
1 motor temperature sensor input, sensors that can be connected: PTC, KTY
and Thermo-Click, accuracy ±5 °C
DC 30 V, 1 A
DC 30 V, 1 A
1 (Differential input)
1 (Non-isolated output)
Mechanical data
203.0 mm
Degree of protection IP20 / UL open type
100.0 mm
Height
Net weight 2.30 kg
Depth
Size
Width
196.0 mm
FSB
Signal cable
Plug-in screw terminals
Version
Version
Unshielded 100 m
Conductor cross-section
Conductor cross-section
4.00 ... 6.00 mm² (12 ... 10 AWG)
Version
4.00 ... 6.00 mm² (12 ... 10 AWG)
Max. motor cable length
Conductor cross-section
Connections
Plug-in screw-type terminals
Motor end
50 m
On housing with M4 screw
Line side
PE connection
Conductor cross-section
DC link (for braking resistor)
Plug-in screw terminals
4.00 ... 6.00 mm² (12 ... 10 AWG)
Shielded
0.15 ... 1.50 mm² (28 ... 16 AWG)
Converter losses to EN 50598-2*
Comparison with the reference converter (90% /
100%)
Efficiency class
-66.06 %
IE2
104.0 W (1.20 %)
177.0 W (2.04 %)
f
150.0 W (1.73 %)
25%
100%
94.0 W (1.09 %)
132.0 W (1.52 %)
73.0 W (0.84 %)
50%
76 W (0.88 %)
50%
87.0 W (1.01 %)
90%
I
The diagram shows the losses for the points (as per standard EN 50598) of the relative torque
generating current (I) over the relative motor stator frequency(f). The values are valid for the basic
version of the converter without options/components.
The percentage values show the losses in relation to the rated apparent power of the converter.
*calculated values; increased by 10% according to the standard
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Generated Fri Jan 13 15:03:49 CET 2017
Page 2 of 2