User Manual
Interconnection
The P-bus connection of the link incorporates an internal DC power supply for 128 load
units, to supply the power for the DESIGO I/O modules. The DESIGO I/O modules are
connected via the P-bus connection using the P-bus coupling module (I/O bar type PTX
1.01). The main supply voltage is derived from a separate AC 24 V transformer.
The PTX1.01 module can supply up to 18 I/O modules. If there are more than 18 I/O
modules, additional supply modules are required.
As described in data sheets CM2M8102 and CM2N8022 a double-insulated safety
transformer to EN 61 558, designed for continuous operation, must be used. At least
conductor G must be protected with a fuse. The transformer must be sized for the
effective load of the equipment in the control panel including the connected field
devices.
For separate control panel construction, please observe grounding precautions (as
described in CM2M8102).
To avoid earth loops, only G0 must be earthed to a central point. The earthing
precautions for the P-bus must be observed (see data sheets CM2M8102 and
CM2N8022).
For load distribution purposes, the G0 connection of the P-bus coupling module (I/O
bar, type PTX1.01) must be connected to G0 of the transformer. The G0 connection
(between PU and PC) of the DP/P-bus link is designed for connection of the P-
bus/remote bus. The remote bus has not yet been released.
Note
230V~
P-bus
coupling
module
PTX1.01
G
G0
PU
PC
PD
DP/ P-bus link
Profibus
(9-pin DSUB, RS485)
G
G0
F1
F2
Ground
G G0 PU G0 PC PD
24V~
*
* Parallel connection of G0
(Terminal 2)
for connection of remote bus
not yet released.
10/12
Siemens Building Technologies DP/P-bus link CK1N9871en
Building Automation 23.04.2003