Siemens Building Technologies Ethernet PROFIBUS Link CK1N9863en
Building Automation 01.05.2002
Use
The E/P link enables data exchange between the SIMATIC S7 automation stations and
SICLIMAT X via PROFIBUS. In this case, the PROFIBUS is implemented physically on
the Ethernet so that the standard Ethernet connection can be used at the SICLIMAT X.
The E/P link can be operated together with other network members on the Ethernet
(e.g. further E/P links or SIMATIC S7 automation stations).
On the PROFIBUS, the E/P link supports the known SICLIMAT PROFIBUS topologies
for process and local bus. The E/P link is a PROFIBUS master and communicates
using the PROFIBUS protocol with SIMATIC S7. Other PROFIBUS protocols such as
PROFIBUS-DP (decentralized peripherals) can be used in parallel.
For support purposes, the E/P link features an integrated web server that can be
accessed via Ethernet using the PC and a standard browser software.
No additional software must be installed on the service PC.
E/P link supports the following services via the integrated web server functionality:
Output of telegram statistics.
Output of PROFIBUS live list.
Output of logging data.
Display of all configurations.
Change of log settings.
Change of diagnostic settings.
Download of device documentation.
Configuration
Typical topology used with Ethernet PROFIBUS links.
SICLIMAT X-OS
Ethernet TCP/IP process bus
SIMATIC S7
E/P Link
SIMATIC S7
PROFIBUS process bus
PROFIBUS local bus