Data Sheet

Interfaces
Number of industrial Ethernet interfaces 2
USB port 1x USB 2.0, 1x USB client
Connection for keyboard/mouse USB / USB
serial interface 2x COM ports (RS 232, RS 485)
Industrial Ethernet
● Industrial Ethernet interface
2x Ethernet (RJ45)
— 100 Mbps
Yes
— 1000 Mbps
No
Integrated Functions
Monitoring functions
● Temperature monitoring
No
● Watchdog
Yes
● Status LEDs
Yes
● Fan
No
EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of
static electricity
±4 kV contact discharge acc. to IEC 61000-4-2; ±8 kV air
discharge acc. to IEC 61000-4-2
Interference immunity against high-frequency electromagnetic fields
● Interference immunity against high frequency
radiation
10 V/m for 80 - 1 000 MHz, 80% AM acc. to IEC 61000-4-3; 3 V/m
for 1.4 - 2 GHz, 80% AM acc. to IEC 61000-4-3; 1 V/m for 2 - 2.7
GHz, 80% AM acc. to IEC 61000-4-3; 10 V for 150 kHz - 80 MHz,
80% AM acc. to IEC 61000-4-6
Interference immunity to cable-borne interference
● Interference immunity on supply cables
±2 kV acc. to IEC 61000-4-4, burst; ±1 kV acc. to IEC 61000-4-5,
surge symmetric; ±2 kV acc. to IEC 61000-4-5, surge asymmetric
● Interference immunity on signal cables >30m
±2 kV acc. to IEC 61000-4-5, surge, length > 30 m
● Interference immunity on signal cables < 30m
±2 kV in accordance with IEC 61000-4-4, burst, length > 30 m
Interference immunity against voltage surge
● asymmetric interference
±2 kV acc. to IEC 61000-4-5, surge asymmetric
● symmetric interference
±1 kV acc. to IEC 61000-4-5, surge symmetric
Interference immunity to magnetic fields
● Interference immunity to magnetic fields at 50
Hz
100A/m; to IEC 61000-4-8
Emission of conducted and non-conducted interference
● Interference emission via line/AC current
cables
EN 61000-6-4:2007 +A1:2011
Degree and class of protection
IP (at the front) IP20
Standards, approvals, certificates
6ES7647-0AA00-1YA2 Subject to change without notice
Page 2/
3
09/16/2019 © Copyright Siemens