Data Sheet

● Input resistance (0 to 600 ohms)
10MΩ
Cable length
● shielded, max.
800m; for U/I, 200 m for R/RTD
Analog outputs
integrated channels (AO) 2
Voltage output, short-circuit protection Yes
Cycle time (all channels), min. 1ms; Dependent on the parameterized interference frequency
suppression; for details, see conversion procedure in manual
Output ranges, voltage
● 0 to 10 V
Yes
● 1 V to 5 V
Yes
● -10 V to +10 V
Yes
Output ranges, current
● 0 to 20 mA
Yes
● -20 mA to +20 mA
Yes
● 4 mA to 20 mA
Yes
Load impedance (in rated range of output)
● with voltage outputs, min.
1kΩ
● with voltage outputs, capacitive load, max.
100nF
● with current outputs, max.
500Ω
● with current outputs, inductive load, max.
1mH
Cable length
● shielded, max.
200m
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign),
max.
16bit
● Integration time, parameterizable
Yes; 2.5 / 16.67 / 20 / 100 ms, acts on all channels
● Interference voltage suppression for
interference frequency f1 in Hz
400 / 60 / 50 / 10
Smoothing of measured values
● parameterizable
Yes
● Step: None
Yes
● Step: low
Yes
● Step: Medium
Yes
● Step: High
Yes
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign),
max.
16bit
Settling time
6ES7511-1CK01-0AB0 Subject to change without notice
Page 9/
19
09/13/2019 © Copyright Siemens