Data Sheet

Potential separation
Potential separation digital inputs
● between the channels
No
● between the channels, in groups of
16
Potential separation digital outputs
● between the channels
No
● between the channels, in groups of
16
Potential separation channels
● between the channels and backplane bus
Yes
● Between the channels and load voltage L+
No
Isolation
Isolation tested with 707 V DC (type test)
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.
0°C
● horizontal installation, max.
60°C; Note derating data for onboard I/O in the manual. Display:
50 °C, at an operating temperature of typically 50 °C, the display
is switched off
● vertical installation, min.
0°C
● vertical installation, max.
40°C; Note derating data for onboard I/O in the manual. Display:
40 °C, at an operating temperature of typically 40 °C, the display
is switched off
Ambient temperature during storage/transportation
● min.
-40°C
● max.
70°C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.
5000m; Restrictions for installation altitudes > 2 000 m, see
manual
Configuration
Programming
Programming language
— LAD
Yes
— FBD
Yes
— STL
Yes
— SCL
Yes
— GRAPH
Yes
Know-how protection
● User program protection/password protection
Yes
● Copy protection
Yes
● Block protection
Yes
Access protection
● Password for display
Yes
6ES7511-1CK01-0AB0 Subject to change without notice