Data Sheet

● Rated value (DC)
24V
Output current
● for signal "1" permissible range for 0 to 60 °C,
max.
10mA; ±10 %
Switching frequency
● with resistive load, max.
100Hz
Cable length
● unshielded, max.
200m
Interrupts/diagnostics/status information
Diagnostics function Yes
Diagnostic messages
● Diagnostic information readable
Yes
● Short-circuit
Yes
Diagnostics indication LED
● Group error SF (red)
Yes
● Status indicator digital output (green)
Yes
● Channel fault indicator F (red)
Yes
Ex(i) characteristics
Module for Ex(i) protection Yes
Maximum values of output circuits (per channel)
● Co (permissible external capacity), max.
90nF
● Io (short-circuit current), max.
70mA
● Lo (permissible external inductivity), max.
6.7mH
● Po (power of load), max.
440mW
● Uo (output no-load voltage), max.
25.2V
Potential separation
Potential separation digital outputs
● Potential separation digital outputs
Yes
● between the channels, in groups of
1
Standards, approvals, certificates
Use in hazardous areas
● Type of protection acc. to EN 50020
(CENELEC)
[EEx ib] IIC
● Type of protection acc. to FM
Class I, Division 2, Group A, B, C, D T4
● Test number PTB
Ex-96.D.2093X
Ambient conditions
Ambient temperature during operation
● max.
60°C
Connection method
required front connector 20-pin
6ES7322-5SD00-0AB0 Subject to change without notice