Datasheet

● Interference voltage suppression for
interference frequency f1 in Hz
85 dB at 50 / 60 / 400 Hz
Errors/accuracies
Temperature error (relative to input range), (+/-) 25 °C ±0.1%, to 55 °C ±0.2% total measurement range
Repeat accuracy in steady state at 25 °C (relative to
output range), (+/-)
0.05%
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Common mode interference, min.
120dB
Interrupts/diagnostics/status information
Alarms Yes
Diagnostics function Yes; Can be read out
Alarms
● Diagnostic alarm
Yes
Diagnostic messages
● Monitoring the supply voltage
Yes
● Wire-break
Yes
Diagnostics indication LED
● for status of the inputs
Yes
● for maintenance
Yes
Degree and class of protection
Degree of protection acc. to EN 60529
● IP20
Yes
Standards, approvals, certificates
CE mark Yes
CSA approval Yes
FM approval Yes
RCM (formerly C-TICK) Yes
Ambient conditions
Free fall
● Fall height, max.
0.3m; five times, in product package
Ambient temperature during operation
● min.
-20°C
● max.
60°C
● horizontal installation, min.
-20°C
● horizontal installation, max.
60°C
● vertical installation, min.
-20°C
● vertical installation, max.
50°C
Ambient temperature during storage/transportation
● min.
-40°C
● max.
70°C
Air pressure acc. to IEC 60068-2-13
6ES7231-5PD32-0XB0 Subject to change without notice
Page 3/
4
01/09/2019 © Copyright Siemens