Instructions

Table Of Contents
Technologieanweisungen
10.2 PID-Regelung
S7-1200 Automatisierungssystem
Systemhandbuch, V4.2.3, 08/2018, A5E02486681-AL
627
10.2.4
PID_Temp
10.2.4.1
Anweisung PID_Temp
Die Anweisung PID_Temp bietet einen universellen PID-Regler für die speziellen
Anforderungen der Temperaturregelung.
Tabelle 10- 26 Anweisung PID_Temp
KOP/FUP
SCL
Beschreibung
"PID_Temp_1"(
Setpoint:=_real_in_,
Input:=_real_in_,
Input_PER:=_int_in_,
Disturbance:=_real_in_,
ManualEnable:=_bool_in_,
ManualValue:=_real_in_,
ErrorAck:=_bool_in_,
Reset:=_bool_in_,
ModeActivate:=_bool_in_,
Mode:=_int_in_,
Master:=_dword_in
Save:=_dword_in
ScaledInput=>_real_out_,
OutputHeat=>_real_out_,
OutputCool=>_real_out_,
OutputHeat_PER=>_int_out_,
OutputCool_PER=>_int_out_,
Out-
putHeat_PWM=>_bool_out_,
Out-
putCool_PWM=>_bool_out_,
SetpointLimit_H=>_bool_out_,
SetpointLimit_L=>_bool_out_,
InputWarn-
ing_H=>_bool_out_,
InputWarn-
ing_L=>_bool_out_,
State=>_int_out_,
Error=>_bool_out_,
ErrorBits=>_dword_out_);
PID_Temp bietet die folgenden Möglichkei-
ten:
Heizen und Kühlen im Prozess mit ver-
schiedenen Aktoren
Integrierte Selbsteinstellung für die
Temperaturregelung
Kaskadenschaltung von mehreren Tem-
peraturen im Prozess, die vom gleichen
Aktor geregelt werden
1
STEP 7 erstellt das Technologieobjekt und den Instanz-DB automatisch, wenn Sie die Anweisung einfügen. Der In-
stanz-DB enthält die Parameter des Technologieobjekts.
2
Im SCL-Beispiel ist "PID_Temp_1" der Name des Instanz-DBs.