Datasheet
Clock
● Hardware clock (real-time clock)
Yes
● Backup time
480h; typical; 12 days min. at 40 °C
● Deviation per day, max.
±60 s per month
Digital inputs
Number of digital inputs 14
● of which inputs usable for technological
functions
6; HSC (High Speed Counting)
integrated channels (DI) 14
m/p-reading Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max.
14; 14 inputs at 55 °C horizontal or 45 °C vertical
Input voltage
● Rated value (DC)
24V; DC at 4 mA nominal
● for signal "0"
5 V DC at 1 mA
● for signal "1"
15 V DC at 2.5 mA
Input current
● for signal "1", typ.
4mA; nominal
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable
0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1
/ 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms
— at "0" to "1", min.
0.1µs
— at "0" to "1", max.
20ms
for interrupt inputs
— parameterizable
Yes
for counter/technological functions
— parameterizable
Yes; Single phase : 3 at 100 kHz & 3 at 30 kHz, differential: 3 at
80 kHz & 3 at 30 kHz
Cable length
● shielded, max.
500m; 50 m for technological functions
● unshielded, max.
300m; 50 m for technological functions
Digital outputs
Number of digital outputs 10; Relays
integrated channels (DO) 10
Short-circuit protection No; to be provided externally
Switching capacity of the outputs
● with resistive load, max.
2A
● on lamp load, max.
30W; 30 W with DC, 200 W with AC
Output delay with resistive load
● "0" to "1", max.
10ms; max.
6ES7215-1HF40-0XB0 Changes preserved
Page 3/
8