Datasheet
● Backup time
480h; typical; 12 days min. at 40 °C
● Deviation per day, max.
±60 s per month
Digital inputs
Number of digital inputs 14
● of which inputs usable for technological
functions
6; HSC (High Speed Counting)
integrated channels (DI) 14
m/p-reading Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max.
14; 14 inputs at 55 °C horizontal or 45 °C vertical
Input voltage
● Rated value (DC)
24V; DC at 4 mA nominal
● for signal "0"
5 V DC at 1 mA
● for signal "1"
15 V DC at 2.5 mA
Input current
● for signal "1", typ.
4mA; nominal
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable
0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1
/ 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms
— at "0" to "1", min.
0.1µs
— at "0" to "1", max.
20ms
for interrupt inputs
— parameterizable
Yes
for counter/technological functions
— parameterizable
Yes; Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @
80 kHz & 3 @ 30 kHz
Cable length
● shielded, max.
500m; 50 m for technological functions
● unshielded, max.
150m; For technological functions: No
Digital outputs
Number of digital outputs 10
● of which high-speed outputs
4; 100 kHz Pulse Train Output
integrated channels (DO) 10
Short-circuit protection No; to be provided externally
Switching capacity of the outputs
● with resistive load, max.
0.5A
● on lamp load, max.
5W
Output voltage
● for signal "0", max.
0.1V; with 10 kOhm load
● for signal "1", min.
20 V
6ES7214-1AF40-0XB0 Changes preserved
Page 3/
8
08.03.2016 © Copyright Siemens AG