User Manual
  Technical specifications 
  A.1 General technical specifications 
Easy Book 
Manual, 03/2014, A5E02486774-AF 
285 
Table A- 3  Conducted and radiated emissions per EN 61000-6-4 
Electromagnetic compatibility - Conducted and radiated emissions per EN 61000-6-4 
Conducted Emissions 
EN 55011, Class A, Group 1 
0.15 MHz to 0.5 MHz 
<79dB (μV) quasi-peak; <66 dB (μV) average 
0.5 MHz to 5 MHz 
<73dB (μV) quasi-peak; <60 dB (μV) average 
5 MHz to 30 MHz 
<73dB (μV) quasi-peak; <60 dB (μV) average 
Radiated Emissions 
EN 55011, Class A, Group 1 
30 MHz to 230 MHz 
<40dB (μV/m) quasi-peak; measured at 10m 
230 MHz to 1 GHz 
<47dB (μV/m) quasi-peak; measured at 10m 
Environmental conditions 
Table A- 4  Transport and storage 
Environmental conditions - Transport and storage 
EN 60068-2-2, Test Bb, Dry heat and  
EN 60068-2-1, Test Ab, Cold 
-40 °C to +70 °C 
EN 60068-2-30, Test Db, Damp heat 
25 °C to 55 °C, 95% humidity 
EN 60068-2-14, Test Na, temperature shock 
-40 °C to +70 °C, dwell time 3 hours, 5 cycles 
EN 60068-2-32, Free fall 
0.3 m, 5 times, product packaging 
Atmospheric pressure 
1080 to 660h Pa (corresponding to an altitude of -1000 to 3500m) 
Table A- 5  Operating conditions 
Environmental conditions - Operating 
Ambient temperature range  
(Inlet Air 25 mm below unit) 
-20 °C to 60 °C horizontal mounting 
-20 °C to 50 °C vertical mounting 
95% non-condensing humidity 
Unless otherwise specified 
Atmospheric pressure 
1080 to 795 hPa (corresponding to an altitude of -1000 to 2000m) 
Concentration of contaminants 
S0
2
: < 0.5 ppm; H
2
S: < 0.1 ppm; RH < 60% non-condensing 
EN 60068-2-14, Test Nb, temperature change 
5 °C to 55 °C, 3 °C/minute 
EN 60068-2-27 Mechanical shock  15 G, 11 ms pulse, 6 shocks in each of 3 axis 
EN 60068-2-6 Sinusoidal vibration  DIN rail mount: 3.5 mm from 5-9 Hz, 1G from 9 - 150 Hz 
Panel Mount: 7.0 mm from 5-9 Hz, 2G from 9 to 150 Hz 
10 sweeps each axis, 1 octave per minute 