Datasheet

Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-)
0.25%
● Current, relative to input range, (+/-)
0.25%
● Resistance, relative to input range, (+/-)
0.15%
● Resistance thermometer, relative to input
range, (+/-)
0.15%
Interference voltage suppression for f = n x (f1 +/- 0.5 %), f1 = interference frequency
● Series mode interference (peak value of
interference < rated value of input range), min.
40dB
Interrupts/diagnostics/status information
Alarms
● Diagnostic alarm
Yes; Parameterizable
● Limit value alarm
Yes; Parameterizable
Diagnostic messages
● Wire-break
Yes; at 4 mA to 20 mA and 1 V to 5 V
● Short-circuit
Yes; Encoder supply to M, channel by channel
● Overflow/underflow
Yes
Diagnostics indication LED
● Channel status display
Yes; green LED
● for module diagnostics
Yes; green/red LED
Potential separation
between the load voltages Yes
Potential separation channels
● between the channels
No
● between the channels and backplane bus
Yes
● between the channels and the power supply of
the electronics
No
Isolation
Isolation tested with 707 V DC (type test)
Degree and class of protection
IP degree of protection IP65/67
Standards, approvals, certificates
Suitable for safety-related tripping of standard
modules
Yes; From FS02
Highest safety class achievable for safety-related tripping of standard modules
● Performance level according to ISO 13849-1
PL d
● Category according to ISO 13849-1
Cat. 3
● SILCL according to IEC 62061
SILCL 2
Ambient conditions
Ambient temperature during operation
6ES7144-5KD00-0BA0 Subject to change without notice
Page 4/
5
02/04/2020 © Copyright Siemens