Datasheet
Input current
Current consumption (rated value) 35mA; without load
from load voltage 1L+ (unswitched voltage) 4A; Maximum value
from load voltage 2L+, max. 4A; Maximum value
Encoder supply
Number of outputs 4
24 V encoder supply
● Short-circuit protection
Yes; per channel, electronic
● Output current, max.
0.5A; Per channel, total current of all channels max. 1 A
Power loss
Power loss, typ. 1.5W
Analog inputs
Number of analog inputs 4
● For current measurement
4
● For voltage measurement
4
● For resistance/resistance thermometer
measurement
4
permissible input voltage for voltage input
(destruction limit), max.
30V
permissible input current for current input (destruction
limit), max.
50mA
Cycle time (all channels), min. 8ms
Technical unit for temperature measurement
adjustable
Yes; Degrees Celsius / degrees Fahrenheit / Kelvin
Input ranges (rated values), voltages
● 0 to +10 V
Yes
— Input resistance (0 to 10 V)
10MΩ
● 1 V to 5 V
Yes
— Input resistance (1 V to 5 V)
10MΩ
Input ranges (rated values), currents
● 0 to 20 mA
Yes
— Input resistance (0 to 20 mA)
50Ω
● 4 mA to 20 mA
Yes
— Input resistance (4 mA to 20 mA)
50Ω
Input ranges (rated values), resistance thermometer
● Ni 100
Yes; Standard/climate
— Input resistance (Ni 100)
10MΩ
● Pt 100
Yes; Standard/climate
— Input resistance (Pt 100)
10MΩ
Input ranges (rated values), resistors
● 0 to 150 ohms
Yes
6ES7144-5KD00-0BA0 Subject to change without notice
Page 2/
5
02/04/2020 © Copyright Siemens