Datasheet

Input current
Current consumption (rated value) 35mA; without load
from load voltage 1L+ (unswitched voltage) 4A; Maximum value
from load voltage 2L+, max. 4A; Maximum value
Encoder supply
Number of outputs 4
24 V encoder supply
● Short-circuit protection
Yes; per channel, electronic
● Output current, max.
0.5A; Per channel, total current of all channels max. 1 A
Power loss
Power loss, typ. 1.5W
Analog inputs
Number of analog inputs 4
● For current measurement
4
● For voltage measurement
4
● For resistance/resistance thermometer
measurement
4
permissible input voltage for voltage input
(destruction limit), max.
30V
permissible input current for current input (destruction
limit), max.
50mA
Cycle time (all channels), min. 8ms
Technical unit for temperature measurement
adjustable
Yes; Degrees Celsius / degrees Fahrenheit / Kelvin
Input ranges (rated values), voltages
● 0 to +10 V
Yes
— Input resistance (0 to 10 V)
10MΩ
● 1 V to 5 V
Yes
— Input resistance (1 V to 5 V)
10MΩ
Input ranges (rated values), currents
● 0 to 20 mA
Yes
— Input resistance (0 to 20 mA)
50Ω
● 4 mA to 20 mA
Yes
— Input resistance (4 mA to 20 mA)
50Ω
Input ranges (rated values), resistance thermometer
● Ni 100
Yes; Standard/climate
— Input resistance (Ni 100)
10MΩ
● Pt 100
Yes; Standard/climate
— Input resistance (Pt 100)
10MΩ
Input ranges (rated values), resistors
● 0 to 150 ohms
Yes
6ES7144-5KD00-0BA0 Subject to change without notice
Page 2/
5
02/04/2020 © Copyright Siemens