Datasheet

● CE marking
Yes
● as approval for USA
cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259;
cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
● relating to ATEX
IECEx nA IIC T5 Gc; ATEX (EX) II 3G Ex nA IIC T5 Gc; cCSAus
(CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group
ABCD, T5
● C-Tick
No
Type of certification CB-certificate Yes
Shipbuilding approval ABS, DNV GL
Protection class IP IP20
EMC
Standard
● for emitted interference
EN 55022 Class B
● for interference immunity
EN 61000-6-2
Operating data
Ambient temperature
● during operation
-25...+60°C; with natural convection
● during transport
-40...+70°C
● during storage
-40...+70°C
Environmental category acc. to IEC 60721 Climate class 3K3; in addition 95% maximum relative humidity,
but without condensation
Mechanics
Type of electrical connection -
● at input
-
● at output
-
● for control circuit and status message
-
Type of connection to system components Via integrated connector
Width of the enclosure 60mm
Height of the enclosure 125mm
Depth of the enclosure 150mm
Required spacing
● top
50mm
● bottom
50mm
● left
0mm
● right
0mm
Net weight 1.33kg
Product feature of the enclosure housing for side-by-
side mounting
Yes
Mounting type Snaps onto DIN rail EN 60715 35x15
Mechanical accessories Device identification label 20 mm × 7 mm, TI-grey 3RT2900-
1SB20
MTBF at 40 °C 4505531h
6EP4297-8HB00-0XY0 Subject to change without notice
Page 2/
3
07/25/2018 © Copyright Siemens