Datasheet

● during transport
-40...+80°C
● during storage
-40...+35°C
Service life
Service life of energy storage
● typical Note
capacity falls to 80 % of original capacity (according to
EUROBAT)
● at 20 °C typical
8y
● at 30 °C typical
4y
● at 40 °C typical
2y
● at 50 °C typical
1y
Mechanics
Connection technology Plug-in terminals with screw connectors
Connection for power supply unit +, -: 2 plug-in terminals with 1 screwed connection each for 0.2 ...
10 mm²
Product component belonging to 2x blade-type fuse 40 A, 58 V DC
Width of the enclosure 322mm
Height of the enclosure 187mm
Depth of the enclosure 110mm
Installation width 322mm
Installation height 207mm
Weight, approx. 6.5kg
Installation keyhole mounting for hooking in to M4 screws
Reference identifier acc. to DIN EN 81346-2 G
Other information Specifications at rated input voltage and ambient temperature +25
°C (unless otherwise specified)
6EP4143-8JB00-0XY0 Subject to change without notice
Page 2/
2
07/27/2018 © Copyright Siemens