Datasheet

● in buffering mode
Buffered mode: LED yellow (Bat), floating changeover contact
"OK/Bat" to setting "Bat"; Prewarning battery voltage < 20.4 VDC:
LED red (alarm), floating changeover contact "Alarm/Bat" to
setting "Alarm"; Energy storage > 85%: LED green (Bat > 85%),
floating NO contact "Bat > 85" closed
Interface
Product component PC interface No
Design of the interface without
Safety
Galvanic isolation between entrance and outlet No
Operating resource protection class Class III
Certificate of suitability
● CE marking
Yes
● as approval for USA
cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
● relating to ATEX
IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc;
cULus Class I, Div. 2 (ANSI/ISA-12.12.01-2015, CSA C22.2 No.
213-15) Group ABCD, T4; cCSAus (CSA C22.2 No. 213,
ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T4
● C-Tick
Yes
Type of certification CB-certificate Yes
Shipbuilding approval ABS, DNV GL
Protection class IP IP20
EMC
Standard
● for emitted interference
EN 55022 Class B
● for interference immunity
EN 61000-6-2
Operating data
Ambient temperature
● during operation
-25...+70°C; with natural convection
● during transport
-40...+85°C
● during storage
-40...+85°C
Environmental category acc. to IEC 60721 Climate class 3K3, no condensation
Mechanics
Type of electrical connection screw-type terminals
● at input
24 V DC: 2 screw terminals for 0.2 ... 6 mm²/24 ... 13 AWG
● at output
24 V DC: 2 screw terminals for 0.2 ... 6 mm²/24 ... 13 AWG
● for battery module
24 V DC: 2 screw terminals for 0.2 ... 6 mm²/24 ... 13 AWG
● for control circuit and status message
14 screw terminals for 0.2 ... 1.5 mm²/24 ... 16 AWG
Width of the enclosure 50mm
Height of the enclosure 125mm
Depth of the enclosure 125mm
Required spacing
6EP4136-3AB00-0AY0 Subject to change without notice
Page 3/
4
04/14/2018 © Copyright Siemens