Datasheet
Formula for output voltage Vin - approx. 0.01 x I
ON-delay time typical 60s
Voltage increase time of the output voltage typical 60ms
Output voltage in buffering mode at DC 19...28.5V
Output current
● Rated value
20A
● in normal operation
0...60A
● in buffering mode
0...60A
Peak current 60A
Property of the output Short-circuit proof Yes
Design of short-circuit protection Limitation to 3 x I rated for 30 ms/min; through-conductivity for 1.5
x I rated for 5 sec/min
Supplied active power typical 480W
Efficiency
Efficiency in percent
● at rated output current for rated value of the
output current typical
98.2%
● in case of accumulator operation typical
98.2%
Power loss [W]
● at rated output current for rated value of the
output current typical
8.6W
● in case of accumulator operation typical
8.6W
Protection and monitoring
Product function
● reverse polarity protection against energy
storage unit polarity reversal
Yes
● reverse polarity protection against input voltage
polarity reversal
Yes
Signaling
Display version
● for normal operation
Normal operation: LED green (OK), floating changeover contact
"Bat/OK" to setting "OK" ("OK" means: Voltage of the supplying
power supply unit is greater than cut-in threshold set at the DC
UPS module); Lack of buffer standby: LED red (alarm), floating
changeover contact "Alarm/Bat" to setting "Alarm"; Battery
replacement required: LED red (alarm) flashing with approx. 0.25
Hz, floating changeover contact "Alarm/Bat" switching with
approx. 0.25 Hz; Energy storage > 85%: LED green (Bat > 85%),
floating NO contact "Bat > 85" closed; Permissible contact current
capacity: DC 60 V/1 A or AC 30 V /1 A
6EP4136-3AB00-0AY0 Subject to change without notice
Page 2/
4
04/14/2018 © Copyright Siemens