3.6 Web server
SITOP UPS1600 / UPS1100
Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
95
The individual columns contain the following information:
● Name: A descriptive name of the alarm
● Time: The time and date when the alarm comes and goes
● Alarm: Alarm type:
– incoming: Occurrence of the alarm event
– outgoing: Rectification of the alarm event
Note
The alarm history is displayed only when no further communications relationships to the
UPS1600 have been established.
Examples for further communications relationships are communi
cation relationships via
STEP 7 V5 or the SITOP UPS Manager.
3.6.7
Configuring the communications interface
Setting the password
1. Select the "Hardware configuration" menu.
2. In the navigation under "Communication interface", select the "LAN" entry.
3. In the fields in the "Password" area, enter the required password.
Both entries must be identical.
4. Load the configuration into the UPS1600 by pressing the "Download to device" button.