3.5 SITOP UPS Manager
SITOP UPS1600 / UPS1100
88 Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
● Battery temperature over time
● Battery charge over time
● Charge current over time
Procedure
1. Select "Monitor > Trend chart".
2. Select "DC UPS Base Unit" to display trend charts for values of the UPS1600
or
Select "Energy storage" to display trend charts of the energy storage values.
3 charts are available under both points.
3. Click the appropriate button to display the required trend chart.
3.5.12
Firmware update
WARNING
The UPS is reset while updating the firmware. For safety reasons, the output is switched
off.
Ensure that no damage is caused to the system and that the PG/PC has a power supply
independent of the UPS during the firmware update.
The files for updating the firmware (firmware updates) are available online under
(http://support.automation.siemens.com/WW/view/de/79207181). Different firmware updates
are offered depending on the amperage of the UPS.
Note
Observe the compatibility of the firmware!
Determine the amperage of your UPS and download the appropriate firmware update. Other
firmware updates are not compatible.
Preconditions
● The UPS1600 is connected correctly and connected with the system.
● PG/PC with SITOP UPS Manager is connected with the system.