3.5 SITOP UPS Manager
SITOP UPS1600 / UPS1100
82 Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
3.5.10
Behavior of the SITOP UPS Manager
The monitoring of the uninterruptible power supply by the SITOP UPS Manager permits
other applications to be started event driven.
In the event of a power failure, the SITOP UPS Manager can use the network to perform a
controlled shutdown of the devices connected to the uninterruptible power supply in the
specified order, or place them in a defined standby state.
The sending of alarms and notifications to the system or to users is also possible (SMS, e-
mail).
The applications can be started depending on the following events and factors:
Supply voltage failure
Restoration of the supply voltage
State of the buffer readiness by the UPS:
General buffer readiness
Remaining buffer time
State of the UPS battery:
Battery charge
Storing an application
In the various submenus, you can store applications that will be started depending on the
above-mentioned events and factors. Examples of such applications are:
Batch scripts, for example, to shut down a computer in the network
Applications that inform the user about the state of the power supply
Applications that protect licenses assigned to computers (floating licenses) from being
lost because of power failure
Procedure
1. Open the appropriate submenu under "Software configuration".
2. Activate the checkbox to start the application for the desired event.
3. To select an application, click on the "Browse" button.
Select the required application from a directory.
The application path is displayed.
4. To check whether the application will performed correctly, click the "Start" button.
5. Enter the time in seconds after which the application should be started.
Note
Only those applications that do not open any Windows screen can b
e started.