User manual
Engineering
3.5 SITOP UPS Manager
SITOP UPS1600 / UPS1100
80 Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
3.5.8
General settings
Under "Software configuration > General settings", specify the maximum size of the log file in
KB and where it is saved.
From SITOP UPS Manager V4.12.5 and higher, under"Software configuration > General
settings" you can also specify as to whether the window of the SITOP UPS Manager should
always be in the foreground.
Log file
1. Select "Software configuration > General settings".
2. Enter the maximum file size in kilobytes in the "Size of log file" dialog box.
3. Click on the "Browse" button and select a directory in which the log file should be saved.
Confirm with "Select folder".
The maximum size and the storage location of the log file has been saved.
3.5.9
Configuring the UPS1600
You can use the SITOP UPS Manager to configure the UPS1600 and its energy storage,
and subsequently load it into the device.
1. To do this, select "Hardware configuration > Base device" or "Hardware configuration >
Energy storage".
2. Enter the desired values.
3. Click on the "Download to device" button
Configuration of the base device
The following parameters are available under "Hardware configuration > Base device":
Parameter
Value range
Default setting
Location-ID
Free text
–
Connection threshold
21 … 25 V
21.5 V
Buffer time
1 … 32,767 s
60 s
Shut down additional PC buffer time
1 … 300 s
10 s
Switch-off time after shutdown
1 … 300 s
5 s
Enable reset after buffering
Yes / No
Yes
Downtime alarm
0 … 20,000 ms
125 ms
Time of the pending input voltage
0.005 … 65 s
0.5 s
● Location ID: Details of the location identification where the UPS1600 is installed.
● Connection threshold: If the connection threshold value is fallen below, the UPSstarts
buffering. If the value of the connection threshold is reached or undershot again later, the
UPS stops buffering.