3.5 SITOP UPS Manager
SITOP UPS1600 / UPS1100
Operating Instructions, 05.2014, C98130-A7628-A1-4-7629
73
5. Follow the installation instructions. Enter the requested information in the dialogs:
User interface language, German or English
Agreement declaration with the license conditions
Installation scope:
Activate the options "Application" and "Driver".
Installation path:
Accept the suggested path:
C:\SITOPUPSManager.
If you change the path, ensure that the path name does not contain any blanks.
Start menu folder
Select the folder structure under which the SITOP UPS Manager should appear in the
start menu.
6. Connect the UPS1600 with the computer via the Ethernet or USB interface.
7. Click "Finish" to complete the installation.
Result
After the successful installation, the SITOP "UPS Manager" is contained in the start menu
under the selected start menu folder.
No further installations are required to operate the SITOP UPS Manager.
Uninstallation
The UPS Manager can be uninstalled using "Start → All programs → SITOP UPS Manager →
Uninstall".
3.5.4
Connection possibilities to the UPS1600
Depending on its type, the UPS1600 provides either a USB interface or an Ethernet
interface.
Depending on its type, the UPS1600 communicates via USB or Ethernet with the SITOP
UPS Manager.
The SITOP UPS Manager supports the master-slave operation only for an existing Ethernet
connection. This permits, for example, a controlled shutdown of the computers in the
network by the applications started with the SITOP UPS Manager.
3.5.5
Establishing a connection via Ethernet
The SITOP UPS1600 requires an IP address for the communication with the UPS Manager.
This is assigned by the network administrator. The Primary Setup Tool is used to configure
the SITOP UPS1600 interface.